Contact

| Model | Capacity (kg/h) | Heating surface (m²) | Thermal capacity (kcal/h) | Thermal capacity (kW) | Efficiency (%) | Back pressure (mbar) | Length (mm) | Width (mm) | Height (mm) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|---|
| WSG150 | 150 | 3.4 | 84750 | 99 | 90 | 1 | 1350 | 900 | 1100 | 775 |
| WSG200 | 200 | 4.4 | 113000 | 131 | 90 | 1 | 1450 | 950 | 1200 | 825 |
| WSG250 | 250 | 5.6 | 141250 | 164 | 90 | 1.2 | 1600 | 950 | 1200 | 900 |
| WSG300 | 300 | 6.6 | 169500 | 197 | 90 | 1.5 | 1650 | 950 | 1200 | 950 |
| WSG400 | 400 | 8.8 | 226000 | 263 | 90 | 1.5 | 1800 | 1100 | 1400 | 1100 |
| WSG500 | 500 | 11.2 | 282500 | 328 | 90 | 2 | 1850 | 1100 | 1400 | 1300 |
| WSG750 | 750 | 16.6 | 423750 | 493 | 90 | 2.5 | 2150 | 1200 | 1500 | 1450 |
| WSG1000 | 1000 | 22.2 | 565000 | 657 | 90 | 3 | 2250 | 1300 | 1500 | 1775 |
| WSG1250 | 1250 | 27.8 | 706250 | 821 | 90 | 3 | 2400 | 1350 | 1650 | 2125 |
| WSG1500 | 1500 | 33.4 | 847500 | 985 | 90 | 3.5 | 2550 | 1400 | 1700 | 2350 |
| WSG2000 | 2000 | 44.4 | 1130000 | 1314 | 90 | 4.5 | 3000 | 1550 | 1750 | 2800 |
| WSG2500 | 2500 | 55.6 | 1412500 | 1642 | 90 | 5 | 3250 | 1600 | 1900 | 3200 |
| WSG3000 | 3000 | 66.6 | 1695000 | 1971 | 90 | 5.5 | 3350 | 1850 | 2100 | 4250 |
| WSG3500 | 3500 | 77.8 | 1977500 | 2299 | 90 | 6.5 | 3900 | 1900 | 2100 | 4800 |
| WSG4000 | 4000 | 88.8 | 2260000 | 2628 | 90 | 7 | 4150 | 1900 | 2100 | 5075 |
| WSG5000 | 5000 | 111.2 | 2825000 | 3285 | 90 | 7.5 | 4650 | 2200 | 2350 | 5950 |
Steam generators rapidly convert water into steam, supplying high-pressure or low-pressure steam. FMT Boiler manufactures them in a capacity range of 100-3,000 kg/h, at steam working pressures of 6-16 bar, gas or liquid fuel fired, with a single or double coil depending on the capacity.
Two types are available: horizontal and vertical.
Fully Automatic Operation System with a PLC-controlled touchscreen panel that uses dedicated software to prevent water carryover and allows all process parameters to be integrated into the system.
Steam generators can generally be more compact and lighter than boilers, which makes them ideal for small spaces or specific applications.

Steam generators typically heat up quickly and can produce steam in a short time. This makes them advantageous when steam needs to be supplied rapidly.
Steam generators are used in industrial processes, laboratories, hospitals, hotels, cooking equipment and many other applications. They are also widely used in the textile, food processing, chemical and pharmaceutical industries.
In water-tube steam generators, water quality plays a critical role in both performance and service life. Water softening and reverse osmosis systems can be used to reduce the mineral content and conductivity of hard water. In addition, controlling the pH by adding chemical treatment agents to the water can reduce the risk of corrosion.
Water Treatment Criteria for Steam Generators:
Water Hardness: < 0.1ºDh.
Conductivity: < 1,000 µS/cm.
Oxygen Content: < 0.05 mg/L.
CO2 (Carbon Dioxide) Limit: <25 mg/L.
Free CO2 Limit: < 0 mg/L.
pH Limit: ~ 8.5-9.5
Metal/Iron Limit: < 0.02 mg/L.
In water-tube steam generators, water quality is a critical factor in efficiency, safety and operating costs. Therefore, properly treating and monitoring the water is essential to ensure the system operates correctly and has a long service life.

Send us your request for this product; our team will get back to you shortly.